80 Amp Mercury Relay - Contactor

Diagrams : 1 Pole     2 Pole     3 Pole    
COIL VOLTAGES: Up to 480 VAC and 250 VDC        Load Rating
Termination: Coil- #6 Binding Head Screw.   Load - Pressure Connector for AWG#2-12 leads.  Pull-in Voltage : Typically less than 80% of nominal.
Drop-out Voltage : Approx 5 volts less than pull-in voltage.
Timing : Contact closing or opening from 70 ms.     Dielectric withstand : 2500V RMS.
Contact Resistance: Typically <.001 ohms.      Temperature Range : -35 to 75 C.       
U.L. standard : meets or exceeds UL & CSA req.
Pricing and Secure On-Line Ordering Here

Catalog # Coil Voltage Coil Current Coil Power Contact
80NO-120AH 120V 50/60Hz 150mA 8 W S.P.S.T. N.O.
280NO-120AH 120V 50/60Hz 300mA 16 W D.P.S.T. N.O.
380NO-120AH 120V 50/60Hz 450mA 24 W T.P.S.T. N.O.
80NC-120AH 120V 50/60Hz 225mA 12 W S.P.S.T. N.C.
280NC-120AH 120V 50/60Hz 450mA 24 W D.P.S.T. N.C.
380NC-120AH 120V 50/60Hz 675mA 36 W T.P.S.T. N.C.